The STS product is designed with two independent power inlets to supply power to the load from a primary power source.
Dual power supply for redundancy
Provides seamless power switch for IT equipmentTransfer time:≤6 ms
Input Source -A is P riority
|
MODEL |
HPS - 1125 |
HPS - 1132 |
HPS - 1145 |
|
AC INPUT |
|||
|
Phases |
single Phase |
||
|
Voltage |
AtC 220V ± 15% (Other voltages can be customized) |
||
|
Frequency |
50/60HZ |
||
|
AC OUTPUTT |
|
||
|
Phases |
single P hase |
||
|
Volatge |
AC 220V± 15% |
||
|
Frequency |
50/60HZ |
||
|
Max Current(/Phase) |
25A |
32A |
40A |
|
Connectors |
Terminal block |
||
|
Breaker |
MCB |
||
|
PERFORNMANCE |
|||
|
Tramsfer Time |
≤ 6 ms(typical) |
||
|
Transfer |
1P (Optional:1 P + N ) |
||
|
Priority |
Input Source -A is Priority |
||
|
Transfer Type |
SCR / First Disconnect Then Connect |
||
|
Efficiency |
≥ 98% |
||
|
DISPLAY |
|||
|
LED |
Working Status |
||
|
LCD(Optional) |
Voltage \ Current\Power |
||
|
OTHER |
|||
|
Colling |
A ir cooling; Ac fan start when over temperature |
||
|
Insulationresistance |
DC 500V ≥ 20MΩ |
||
|
Insulation withstand voltage |
AC1800V 10mA/ 1 Minute |
||
|
Operating Temperature |
0℃~45℃ |
||
|
Relative humidity |
0 ~99%( Non -condensing) |
||
|
Operating Altitude |
≤ 1 500m |
||
|
Dimensions(W*D*H) |
430*350*88m m |
||
|
Net Weight |
11kg |
12kg |
13kg |